What Size Wire for a 40 Amp Breaker?
Use 8 AWG for a 40 amp breaker, in either copper or aluminum. 8 AWG copper is rated 40 A at 60 °C and 50 A at 75 °C, so it works with common terminals.
The answer
8 AWG copper
8 AWG aluminum (75 °C terminals)
| Case | Wire size | Table ampacity | Area |
|---|---|---|---|
| Copper · 75 °C THHN in conduit, most modern equipment | 8 AWG | 50 A | 8.4 mm² |
| Copper · 60 °C NM / Romex cable, older terminals | 8 AWG | 40 A | 8.4 mm² |
| Aluminum · 75 °C Needs connectors and terminals listed for aluminum | 8 AWG | 40 A | 8.4 mm² |
On this page
How the answer is worked out
The breaker is 40 A. The smallest copper wire with a 75 °C table ampacity at or above 40 A is 8 AWG, rated 50 A, with a cross-section of 8.4 mm².
For 60 °C terminals or NM cable the smallest copper size is 8 AWG, rated 40 A in the 60 °C column.
Aluminum uses its own column. The smallest aluminum size at 75 °C for this rating is 8 AWG, rated 40 A. Aluminum conductors need connectors and terminals listed for aluminum.
This example treats the load as continuous (three hours or more). 32 A × 1.25 = 40 A, so the next standard breaker is 40 A and the wire must carry at least that much.
NEC 240.4(D) also limits the breaker for small conductors: 14 AWG copper is capped at 15 A, 12 AWG copper at 20 A, 10 AWG copper at 30 A, 12 AWG aluminum at 15 A and 10 AWG aluminum at 25 A. The sizes in the table respect those caps, so a wire is never paired with a breaker larger than its limit.
Why 8 AWG
10 AWG is limited to a 30 amp breaker, so 8 AWG is the next size. It carries 40 A even in the 60 °C column, which is the one used for NM cable, so it is fine for a 40 amp breaker with either NM cable or individual wires in conduit.
EV chargers on a 40 amp breaker
EV charging counts as a continuous load, so the circuit is sized at 125% of the charger's current. A charger that draws 32 A needs a 40 A circuit (32 × 1.25 = 40). A charger that draws 40 A needs a 50 amp circuit instead; see the 50 amp guide.
Long runs
Garage-to-driveway and outbuilding runs often exceed 100 ft. Use the distance table below to check whether 8 AWG still keeps the drop under 3%, or step up to 6 AWG.
How far can you run it? (3% voltage drop)
The distance table uses the same resistance-only model as the calculator, with a 3% limit and the wire at 75 °C. Aluminum has about 1.6 times the resistance of copper for the same size, so an aluminum run of the same length drops more voltage.
Assumes the full 40 A load on a single-phase 240 V circuit, a 75 °C conductor, copper or aluminum, a 3% voltage drop limit and the one-way length in the table. Aluminum shows a dash where that size cannot carry the full current.
| Wire size | Copper | Aluminum |
|---|---|---|
| 8 AWG | 115.5 ft [35.2 m] | 70.1 ft [21.4 m] |
| 6 AWG | 183.6 ft [56.0 m] | 111.5 ft [34.0 m] |
| 4 AWG | 292.0 ft [89.0 m] | 177.3 ft [54.1 m] |
| 3 AWG | 368.2 ft [112.2 m] | 223.6 ft [68.2 m] |
Need a specific distance? See: What Size Wire for an EV Charger?
Before you buy wire
The table is a starting point. Work through this list before you order conductors, and keep the answer that matches your real installation.
- Read the equipment nameplate and the breaker. A manufacturer's required circuit size overrides any general table.
- Check the terminal rating on the breaker, the panel lugs and the equipment. Use the 60 °C or 75 °C column that matches the lowest rated part.
- Identify the cable type. NM (Romex) cable is limited to the 60 °C column by NEC 334.80, while conductors in conduit are usually rated 75 °C or higher.
- Measure the one-way distance from the panel to the load, then check voltage drop with the table or the calculator. If the run is long, go up one size.
- Confirm the design with your local code, the authority having jurisdiction and a licensed electrician before you cut wire or install a breaker.
This is general information based on NEC tables, not a permit or an installation plan. Local amendments, the equipment nameplate and an inspector decide what is acceptable. Read the disclaimer.