What Size Wire for a 30 Amp Breaker?
Use 10 AWG copper for a 30 amp breaker. If you use aluminum, step up to 8 AWG, because 10 AWG aluminum is limited to a 25 amp breaker.
The answer
10 AWG copper
8 AWG aluminum (75 °C terminals)
| Case | Wire size | Table ampacity | Area |
|---|---|---|---|
| Copper · 75 °C THHN in conduit, most modern equipment | 10 AWG | 35 A | 5.3 mm² |
| Copper · 60 °C NM / Romex cable, older terminals | 10 AWG | 30 A | 5.3 mm² |
| Aluminum · 75 °C Needs connectors and terminals listed for aluminum | 8 AWG | 40 A | 8.4 mm² |
On this page
How the answer is worked out
The breaker is 30 A. The smallest copper wire with a 75 °C table ampacity at or above 30 A is 10 AWG, rated 35 A, with a cross-section of 5.3 mm².
For 60 °C terminals or NM cable the smallest copper size is 10 AWG, rated 30 A in the 60 °C column.
Aluminum uses its own column. The smallest aluminum size at 75 °C for this rating is 8 AWG, rated 40 A. Aluminum conductors need connectors and terminals listed for aluminum.
NEC 240.4(D) also limits the breaker for small conductors: 14 AWG copper is capped at 15 A, 12 AWG copper at 20 A, 10 AWG copper at 30 A, 12 AWG aluminum at 15 A and 10 AWG aluminum at 25 A. The sizes in the table respect those caps, so a wire is never paired with a breaker larger than its limit.
Why 10 AWG copper works
10 AWG copper is rated 30 A at the 60 °C column and 35 A at 75 °C, and NEC 240.4(D) allows it to be protected at 30 A. 12 AWG is limited to 20 A and is too small.
Common 30 amp uses
Thirty-amp circuits typically feed electric dryers, tank water heaters and 30 amp RV or trailer outlets. Check the nameplate on your appliance: the manufacturer's required circuit size always overrides a general chart.
Aluminum
10 AWG aluminum is limited to a 25 amp breaker under NEC 240.4(D), so a 30 amp breaker needs 8 AWG aluminum. Use connectors and lugs rated for aluminum.
How far can you run it? (3% voltage drop)
The distance table uses the same resistance-only model as the calculator, with a 3% limit and the wire at 75 °C. Aluminum has about 1.6 times the resistance of copper for the same size, so an aluminum run of the same length drops more voltage.
Assumes the full 30 A load on a single-phase 240 V circuit, a 75 °C conductor, copper or aluminum, a 3% voltage drop limit and the one-way length in the table. Aluminum shows a dash where that size cannot carry the full current.
| Wire size | Copper | Aluminum |
|---|---|---|
| 10 AWG | 96.8 ft [29.5 m] | 58.8 ft [17.9 m] |
| 8 AWG | 154.0 ft [46.9 m] | 93.5 ft [28.5 m] |
| 6 AWG | 244.9 ft [74.6 m] | 148.7 ft [45.3 m] |
| 4 AWG | 389.3 ft [118.7 m] | 236.5 ft [72.1 m] |
Need a specific distance? See: What Size Wire for 30 Amps at 100 Feet? , 12V Wire Size Chart: Amps vs Length
Before you buy wire
The table is a starting point. Work through this list before you order conductors, and keep the answer that matches your real installation.
- Read the equipment nameplate and the breaker. A manufacturer's required circuit size overrides any general table.
- Check the terminal rating on the breaker, the panel lugs and the equipment. Use the 60 °C or 75 °C column that matches the lowest rated part.
- Identify the cable type. NM (Romex) cable is limited to the 60 °C column by NEC 334.80, while conductors in conduit are usually rated 75 °C or higher.
- Measure the one-way distance from the panel to the load, then check voltage drop with the table or the calculator. If the run is long, go up one size.
- Confirm the design with your local code, the authority having jurisdiction and a licensed electrician before you cut wire or install a breaker.
This is general information based on NEC tables, not a permit or an installation plan. Local amendments, the equipment nameplate and an inspector decide what is acceptable. Read the disclaimer.