What Size Wire for a 30 Amp Breaker?

Use 10 AWG copper for a 30 amp breaker. If you use aluminum, step up to 8 AWG, because 10 AWG aluminum is limited to a 25 amp breaker.

The answer

10 AWG copper

8 AWG aluminum (75 °C terminals)

Wire size for a 30 amp breaker
Case Wire size Table ampacity Area
Copper · 75 °C THHN in conduit, most modern equipment 10 AWG 35 A 5.3 mm²
Copper · 60 °C NM / Romex cable, older terminals 10 AWG 30 A 5.3 mm²
Aluminum · 75 °C Needs connectors and terminals listed for aluminum 8 AWG 40 A 8.4 mm²

Calculate for your exact distance

On this page

How the answer is worked out

The breaker is 30 A. The smallest copper wire with a 75 °C table ampacity at or above 30 A is 10 AWG, rated 35 A, with a cross-section of 5.3 mm².

For 60 °C terminals or NM cable the smallest copper size is 10 AWG, rated 30 A in the 60 °C column.

Aluminum uses its own column. The smallest aluminum size at 75 °C for this rating is 8 AWG, rated 40 A. Aluminum conductors need connectors and terminals listed for aluminum.

NEC 240.4(D) also limits the breaker for small conductors: 14 AWG copper is capped at 15 A, 12 AWG copper at 20 A, 10 AWG copper at 30 A, 12 AWG aluminum at 15 A and 10 AWG aluminum at 25 A. The sizes in the table respect those caps, so a wire is never paired with a breaker larger than its limit.

Why 10 AWG copper works

10 AWG copper is rated 30 A at the 60 °C column and 35 A at 75 °C, and NEC 240.4(D) allows it to be protected at 30 A. 12 AWG is limited to 20 A and is too small.

Common 30 amp uses

Thirty-amp circuits typically feed electric dryers, tank water heaters and 30 amp RV or trailer outlets. Check the nameplate on your appliance: the manufacturer's required circuit size always overrides a general chart.

Aluminum

10 AWG aluminum is limited to a 25 amp breaker under NEC 240.4(D), so a 30 amp breaker needs 8 AWG aluminum. Use connectors and lugs rated for aluminum.

How far can you run it? (3% voltage drop)

The distance table uses the same resistance-only model as the calculator, with a 3% limit and the wire at 75 °C. Aluminum has about 1.6 times the resistance of copper for the same size, so an aluminum run of the same length drops more voltage.

Assumes the full 30 A load on a single-phase 240 V circuit, a 75 °C conductor, copper or aluminum, a 3% voltage drop limit and the one-way length in the table. Aluminum shows a dash where that size cannot carry the full current.

Maximum one-way length for 3% drop at 30 A, 240 V, 75 °C conductor
Wire size Copper Aluminum
10 AWG 96.8 ft [29.5 m] 58.8 ft [17.9 m]
8 AWG 154.0 ft [46.9 m] 93.5 ft [28.5 m]
6 AWG 244.9 ft [74.6 m] 148.7 ft [45.3 m]
4 AWG 389.3 ft [118.7 m] 236.5 ft [72.1 m]

Need a specific distance? See: What Size Wire for 30 Amps at 100 Feet? , 12V Wire Size Chart: Amps vs Length

Before you buy wire

The table is a starting point. Work through this list before you order conductors, and keep the answer that matches your real installation.

This is general information based on NEC tables, not a permit or an installation plan. Local amendments, the equipment nameplate and an inspector decide what is acceptable. Read the disclaimer.